How to Calculate Power Factor
In an AC circuit, power factor (PF) is the ratio of real power (P, measured in watts or kW) — the power that actually does useful work, like turning a motor shaft or producing heat — to apparent power (S, measured in volt-amps or kVA) — the total power the source must supply to deliver that real power. PF = P ÷ S = cos(θ), where θ is the phase angle between the voltage and current waveforms. Power factor ranges from 0 to 1 (or 0-100%); a purely resistive load (a heater, an incandescent bulb) has PF = 1, while inductive loads like motors and transformers pull PF below 1.
The power triangle: real, reactive, and apparent power
- Real power (P): the working power, in watts (W) or kilowatts (kW), that performs mechanical work or is converted to heat and light.
- Reactive power (Q): in volt-amps-reactive (VAR) or kVAR, the power that oscillates back and forth between the source and the magnetic field of an inductive load (motors, transformers, ballasts) or the electric field of a capacitive load. It does no net work but still requires current-carrying capacity.
- Apparent power (S): in volt-amps (VA) or kVA, the vector sum of real and reactive power: S² = P² + Q², so Q = √(S² − P²). This is the total current × voltage the generator, transformer, and wiring must be sized to deliver, even though only the P portion does useful work.
- Phase angle (θ): the angle between the voltage and current waveforms in the power triangle, where PF = cos(θ) and θ = arccos(PF).
Single-phase vs. three-phase apparent power
- Single-phase circuits: apparent power is simply S = V × I, where V is the RMS voltage and I is the RMS current.
- Balanced three-phase circuits: using line-to-line voltage (V_LL) and line current (I_L), apparent power is S = √3 × V_LL × I_L ≈ 1.732 × V_LL × I_L. The √3 factor accounts for the 120° phase separation between the three phase conductors.
- Once you know S and the real power P (read from a wattmeter or nameplate), power factor follows directly: PF = P ÷ S.
Common mistakes and correcting a low power factor
- Real power can never exceed apparent power — if your calculated P is larger than V × I, double-check that the voltage and current are RMS values for the same load and phase configuration.
- Mixing per-phase and line values in a three-phase system produces a result off by a factor of √3 — be consistent about whether voltage/current are per-phase or line quantities.
- A low power factor (below ~0.90) is usually caused by inductive loads such as motors, transformers, and fluorescent/HID lighting ballasts running under light load.
- Utilities often add a surcharge when PF drops below 0.90-0.95, since they must deliver more current — and lose more energy to I²R heating — for the same billed kWh. Adding capacitor banks near the load supplies local reactive power and raises the measured PF toward unity without changing the real power consumed.