Formula and Method for Mixed Air Temperature
In an HVAC air handling unit (AHU), outdoor air (OA) brought in for ventilation and return air (RA) recirculated from the building merge in a mixing plenum before passing over the heating or cooling coil. The mixed air temperature (MAT) is the flow-weighted average of the two streams' temperatures:
MAT = (CFMOA × TOA + CFMRA × TRA) / (CFMOA + CFMRA)
where CFM is the volumetric airflow rate of each stream (cubic feet per minute) and T is each stream's dry-bulb temperature. Because this is a linear weighted average, it produces a consistent result whether temperatures are entered in Fahrenheit or Celsius — no conversion to an absolute scale like Kelvin is required, unlike ratio-based thermodynamic formulas such as Carnot efficiency.
Deriving the mixing equation from an energy balance
The mixing equation follows from conservation of energy applied to the adiabatic mixing of two air streams. The sensible heat carried by each stream is approximately Q = ṁ × cp × T, where ṁ is mass flow rate and cp is the specific heat of air. Because outdoor air and return air have nearly identical density and specific heat at typical building conditions, mass flow rate is proportional to volumetric flow rate (CFM), and the cp terms cancel out of the balance ṁOAcpTOA + ṁRAcpTRA = (ṁOA + ṁRA)cpTMAT. Solving for TMAT leaves the CFM-weighted average shown above. This simplification is standard in HVAC design practice (per ASHRAE Fundamentals) and is accurate to a fraction of a degree across typical comfort-conditioning temperature ranges.
Freeze protection and economizer control
MAT is not just an intermediate number — it drives two real control decisions in an AHU. First, many units include a low-limit thermostat ("freezestat") that trips when MAT drops too low, commonly around 35-40°F (roughly 2-4°C), because cold, humid mixed air can freeze the water inside a hydronic coil and split the tubes; the controller responds by closing the outdoor air damper and/or opening the heating valve. Second, in "economizer" mode, the building automation system modulates the outdoor air damper position specifically to hit a target MAT close to the supply-air setpoint, so the AHU can use cool outdoor air for free cooling instead of running mechanical refrigeration.