kVA Calculator

Enter voltage, current, and power factor for a single-phase or three-phase circuit to find apparent power (kVA), real power (kW), reactive power (kVAR), and the phase angle.

Quick Facts

Single-phase kVA
kVA = (V × I) / 1000
Voltage times current, divided by 1000 to convert VA to kVA.
Three-phase kVA
kVA = (√3 × V × I) / 1000
V is line-to-line voltage; √3 ≈ 1.732 accounts for the 120° phase offset.
Real power
kW = kVA × PF
Power factor (PF) is the fraction of apparent power doing real work.
Power triangle
kVA² = kW² + kVAR²
Apparent, real, and reactive power form a right triangle.

Your Results

Calculated
Apparent Power
-
kVA = V × I / 1000 (× √3 for three-phase)
Real Power
-
kW = kVA × power factor
Reactive Power
-
kVAR = kVA × sin(θ)
Phase Angle
-
θ = cos⁻¹(power factor)

Ready

Enter voltage, current, and power factor, then press Calculate.

About the kVA Calculator

kVA (kilovolt-amperes) measures apparent power — the combined effect of voltage and current flowing through an AC circuit, regardless of how much of that power actually does useful work. It is the standard rating used for generators, transformers, and UPS systems, because that equipment must be sized for the full current it carries, not just the real power delivered. This calculator finds apparent power (kVA), real power (kW), reactive power (kVAR), and the phase angle from voltage, current, and power factor, for both single-phase and three-phase circuits.

Understanding the formula

For a single-phase circuit, apparent power is simply voltage times current: kVA = (V × I) / 1000, where V is in volts and I is in amps (dividing by 1000 converts volt-amps to kilovolt-amps). For a balanced three-phase circuit, kVA = (√3 × V × I) / 1000, where V is the line-to-line voltage and √3 ≈ 1.7321 accounts for the 120° phase offset between the three legs. Apparent power, real power, and reactive power form a right triangle — the "power triangle" — where kVA is the hypotenuse: (kVA)² = (kW)² + (kVAR)². Real power is kW = kVA × PF, and reactive power is kVAR = kVA × sin(θ), where θ = cos⁻¹(PF) is the phase angle between voltage and current.

Single-phase vs. three-phase circuits

Residential circuits and small appliances are almost always single-phase. Industrial equipment, large motors, and commercial buildings typically run on three-phase power because it delivers more power per conductor and produces smoother torque in motors. The most common mistake when sizing three-phase kVA is entering line-to-neutral voltage instead of line-to-line voltage — line-to-line voltage is √3 times larger (for example, a 230 V line-to-neutral system corresponds to about 400 V line-to-line), so using the wrong one misstates the result by a factor of √3.

Why kVA matters for equipment sizing

Generators, transformers, and UPS units are rated in kVA rather than kW because their windings and conductors must handle the full current flowing through them, regardless of power factor. A load with a low power factor draws more current for the same real power, so equipment sized only in kW could be undersized. As a rule of thumb, size backup power and transformers with 20-25% headroom above the calculated kVA to allow for inrush currents, future load growth, and non-unity power factor loads like motors and electronics.

Frequently Asked Questions

What is kVA and how is it different from kW?
kVA (kilovolt-amperes) measures apparent power — the total power a circuit delivers, combining the power that does useful work with the power that is stored and returned by inductive or capacitive loads. kW measures only the real, usable power. The two are related by the power factor: kW = kVA × PF. A power factor of 1 means all apparent power is real power; anything less means some of the circuit's capacity is reactive and not converted into work.
How do I convert kVA to kW, or kW to kVA?
Multiply kVA by the power factor to get kW: kW = kVA × PF. To go the other way, divide kW by the power factor: kVA = kW ÷ PF. For example, a 10 kVA generator running at a 0.8 power factor can supply 8 kW of real power to the load.
Why does three-phase kVA use √3 instead of just multiplying voltage by current?
In a balanced three-phase system, the three phase currents are 120° apart, so simply multiplying line voltage by line current would overstate the power. The factor √3 (≈1.732) corrects for this phase offset when using line-to-line voltage, giving kVA = (√3 × V × I) / 1000. Single-phase circuits have no phase offset to correct for, so they use kVA = (V × I) / 1000 directly.