About the HP to Amps Calculator
This tool converts a motor's horsepower rating into the electrical current (amperage) it draws from its power supply. It uses the standard electrical engineering relationship between mechanical power, electrical power, voltage, and current, and covers the three common supply types: DC, single-phase AC, and three-phase AC.
Understanding the formula
Every version of the formula starts by converting horsepower to watts using 1 HP = 746 W (the standard NEMA/NEC electrical conversion). From there, the current formula depends on supply type: for DC, I = (HP × 746) / (V × η); for single-phase AC, I = (HP × 746) / (V × η × PF); and for three-phase AC, I = (HP × 746) / (V × η × PF × √3). Here V is the supply voltage, η (eta) is motor efficiency written as a decimal, and PF is the power factor. For example, a 5 HP single-phase motor running at 230V, 85% efficient with a 0.85 power factor, draws about 22.4 A.
Efficiency, power factor, and phase type
Efficiency (η) accounts for the energy a motor loses to heat and friction — it is always less than 100%, typically 80-95% for common induction motors, and is printed on the nameplate. Power factor (PF) applies only to AC circuits: it measures how much of the current actually does mechanical work versus how much is reactive current that the source still has to supply, typically 0.80-0.90 for induction motors near full load. DC circuits have no reactive component, so PF is effectively 1. The extra √3 (≈ 1.732) in the three-phase formula exists because three-phase power is delivered across three lines that are 120° apart, so per-line current is lower than the single-phase case for the same total power.
Knowing the limits
This calculator reports the theoretical full-load current (FLA) at rated output — a steady-state estimate, not the starting (locked-rotor) current, which for AC induction motors can be 5 to 8 times higher for a brief moment at startup. Actual current also shifts with voltage fluctuations, motor loading below rated capacity, and manufacturing tolerances. Never use the raw result here to size wiring or breakers directly; the National Electrical Code (NEC 430.22 and related tables) generally requires a safety margin, commonly 125% of FLA for a single continuous-duty motor, and you should always check the motor's nameplate FLA when it is available.