100 Amp Wire Size Calculator

Find the copper or aluminum wire gauge for your circuit using NEC ampacity ratings and the standard voltage-drop formula for your length, voltage, and phase.

Quick Facts

Ampacity baseline
3 AWG copper or 1 AWG aluminum carries 100A
Per NEC Table 310.16, 75°C column — the minimum size before voltage drop is considered.
Voltage-drop formula
VD = (2 × K × I × D) / CM
Use 1.732 instead of 2 for three-phase; K = 12.9 (copper) or 21.2 (aluminum) ohm-cmil/ft.

Your Results

Calculated
Recommended wire size
-
Meets ampacity and voltage-drop targets
Voltage drop at this size
-
Volts and % of circuit voltage
Ampacity-only minimum
-
NEC 75°C table, current alone
Voltage-drop-only minimum
-
Based on length and max drop target

Ready

Enter your current, voltage, length, and material, then press Calculate.

Understanding 100 Amp Wire Sizing

Sizing a wire for a 100 amp circuit means satisfying two independent requirements at once: the conductor must be rated to carry 100A continuously without overheating (ampacity), and it must be thick enough that the voltage lost to resistance over its length stays within an acceptable percentage (voltage drop). This calculator checks both requirements and recommends whichever gauge is larger — that larger size is the one that actually works.

The ampacity requirement

NEC Table 310.16 lists how much current a given wire gauge and insulation type can carry continuously. At the commonly used 75°C column (THWN, THW), 3 AWG copper or 1 AWG aluminum is rated for exactly 100A — the minimum size for a straight 100A load. A smaller gauge is not permitted regardless of run length, because it would overheat under sustained load.

The voltage-drop formula

Even when a wire is rated to carry the current, a long run can lose too much voltage to resistance before it reaches the load. The standard formula is VD = (2 × K × I × D) / CM for single-phase circuits, or VD = (1.732 × K × I × D) / CM for three-phase, where I is current in amps, D is the one-way length in feet, CM is the conductor's cross-sectional area in circular mils, and K is a resistivity constant — 12.9 ohm-cmil/ft for copper, 21.2 for aluminum. Rearranging for the required circular mils shows the smallest conductor area that keeps drop under your target percentage.

Reading the results

The calculator finds the smallest wire that satisfies ampacity alone, the smallest that satisfies voltage drop alone, and recommends whichever is larger. Short runs are almost always ampacity-limited, so 3 AWG copper is enough. Longer runs at 100A often become voltage-drop-limited and need a larger gauge, even though 3 AWG would technically carry the current safely.

Assumptions and limits

  • Ampacity uses the NEC 75°C column, the most common rating for building wire; the 60°C and 90°C columns give different numbers and may apply depending on your terminals and insulation type.
  • The voltage-drop constant K assumes typical building temperatures and does not correct for conduit fill, heavy derating, or unusual ambient heat.
  • This tool sizes the conductor only — it does not size the circuit breaker or overcurrent device, which follows separate NEC rules. For any permit-required installation, confirm sizing with a licensed electrician.

Frequently Asked Questions

What size wire do I need for 100 amps?
For a straight 100A load, NEC Table 310.16 (75°C column) sets the minimum at 3 AWG copper or 1 AWG aluminum. That is the ampacity-only answer — if your run is long, voltage drop may require a larger gauge, which is what the voltage-drop-limited result above accounts for.
What is voltage drop and why does it matter?
Voltage drop is voltage lost to a conductor's resistance over its length. Excess drop wastes energy as heat and can make motors, appliances, and electronics run below their rated voltage. The NEC recommends keeping voltage drop at or below 3% for a branch circuit and 5% for a feeder plus branch circuit combined.
Should I use copper or aluminum wire for a 100A circuit?
Copper has lower resistance (K = 12.9 ohm-cmil/ft versus 21.2 for aluminum), so it reaches the same voltage-drop target with a smaller gauge. Aluminum is lighter and often less expensive for large feeders, but it typically needs to be sized about two gauges larger than copper and requires anti-oxidant compound at every termination.
How much does wire length affect the size I need?
Voltage drop rises in direct proportion to the one-way length, so doubling the distance roughly doubles the required conductor area to hold the same drop percentage. That is why a short 100A run may only need 3 AWG copper while a long run of the same load can require 1 AWG or larger.