About the 220 Volt Wire Size Calculator
This tool sizes the conductor for a 220-240V circuit — the kind used for dryers, ranges, water heaters, window and central air conditioners, welders, and EV chargers — using the two checks an electrician runs by hand: the National Electrical Code (NEC) ampacity table, and the voltage-drop formula for the actual length of the run.
Step 1: required ampacity
The conductor must be rated for at least the load current. If the load is continuous (expected to run 3 hours or more, such as an AC compressor or EV charger), NEC 210.19(A) requires sizing for 125% of the load current: Required ampacity = Load current x 1.25. Non-continuous loads (a range, a dryer cycling on and off) only need to be sized for the actual current.
Step 2: minimum gauge from the ampacity table
The calculator compares that required ampacity against NEC Table 310.16 (75°C column, the typical rating for THHN/THWN-2 residential branch-circuit wire) to find the smallest copper or aluminum gauge whose listed ampacity meets or exceeds it — for example, 30A calls for 10 AWG copper, while 50A calls for 8 AWG copper.
Step 3: check voltage drop over the run
Ampacity alone ignores wire length. Every conductor has resistance, so current flowing through it drops some voltage before reaching the load. The standard formula, using circular-mil wire area, is:
VD = (2 x K x I x D) / CM
where K is a resistivity constant (12.9 for copper, 21.2 for aluminum, in ohm-cmil/ft), I is the load current in amps, D is the one-way distance in feet, and CM is the conductor's cross-sectional area in circular mils. The factor of 2 accounts for the round trip through both the hot and neutral/return conductors. Dividing VD by the circuit voltage gives the percentage drop. If that percentage exceeds your target (commonly 3% for a branch circuit), the calculator steps up to the next larger gauge and rechecks, repeating until the drop is within limit or the table is exhausted.
Copper vs. aluminum
Aluminum has roughly 61% of copper's conductivity, so it needs a larger cross-section for the same current and voltage-drop target — commonly about two AWG sizes bigger than the equivalent copper run — and NEC does not list aluminum below 12 AWG. This calculator applies the correct ampacity table and K constant for whichever material you select.
Limits of this calculator
This is a planning estimate, not a code inspection. It does not account for ambient-temperature derating, conduit fill and conductor bundling adjustments, terminal temperature ratings, or local amendments to the NEC. Always verify the final wire size and breaker against your local electrical code, and have the installation inspected by a licensed electrician.