Generator Runtime Formula
Generator runtime is based on the amount of usable fuel and the burn rate at the electrical load you expect to run. For a liquid-fuel generator, use compatible gallon units:
Estimated runtime (hours) = usable fuel (gal) ÷ consumption (gal/hr)
Fuel per day (gal/day) = consumption (gal/hr) × run hours per dayUse the consumption rate from the exact generator’s manual or specification table at a load close to your expected demand. Do not substitute the generator’s rated watts, engine size, or a generic fuel-use rule for the burn rate. Manufacturers often publish different consumption values at different load percentages.
Worked Example
If 5 gallons are usable and the manual lists consumption of 0.45 gal/hr at the expected load, the simple estimate is 5 ÷ 0.45 = 11.1 hours. At 12 hours of operation per day, that same rate implies 5.4 gallons per day. The calculator can also multiply that daily use by a user-entered local fuel price.
Use the Right Fuel and Load Data
Consumption depends on generator model, fuel type, load, operating conditions, and measurement basis. For a dual-fuel machine, use the table for the selected fuel. If the manual gives runtime at a known tank size and load instead of a burn rate, divide the stated usable fuel amount by that runtime to estimate an average rate for that test point; do not assume the rate stays constant at other loads.
Generac’s fuel-use guidance directs owners to use model-specific fuel consumption information; its portable-generator manual shows why fuel type and load matter. Natural-gas generators commonly report gas flow in cubic feet per hour, which is not interchangeable with liquid gallons per hour; use a separate estimate with matched units for gaseous fuel.
Planning Limits and Safe Operation
The result assumes a constant burn rate and that all entered fuel is usable. Real runtime can differ because of changing electrical load, unusable tank volume, fuel temperature, maintenance, altitude, and operating conditions. Leave a reserve for shutdown, refueling access, and changing loads rather than planning to exhaust the tank.
Run portable generators outdoors and away from doors, windows, and vents, following the manufacturer’s carbon-monoxide and fire-safety instructions. This tool is a fuel-planning estimate; it does not size a generator for connected equipment or determine safe installation, transfer-switch requirements, or code compliance.